Current clamp TP-CC80
The Current clamp TP-CC80 is a current clamp that will allow your oscilloscope to measure electrical currents up to 80 Ampère AC/DC, with a frequency response up to 20 kHz. When measuring with this current clamp, there is no need to break a closed circuit or to affect the isolation.
The long, narrow jaws allow performing measurements in narrow spaces.
For measuring DC current, a simple to operate zero adjust button is available.
To connect the Current clamp TP-CC80 to your oscilloscope, a BNC to banana measure lead is required, which must be ordered separately. For oscilloscopes with differential inputs, the Measure lead TP-C812B is recommended. For oscilloscopes with single-ended inputs the Measure lead TP-BNCI-100 is recommended.
Order code: TP-CC80
EAN: 7423635782715
Price: 123.40
Category: Current Clamps
The table below shows detailed specifications of the Current clamp TP-CC80.
Electrical | |
|---|---|
| Bandwidth | DC to 20 kHz (-3dB) |
| Effective measurement range | |
| 20 A range | output 100 mV/A, 1 V = 10 A |
| 80 A range | output 10 mV/A, 1 V = 100 A |
| Accuracy | |
| DC 20 A range | ±(3% ±5 mA) |
| DC 80 A range | ±(3% ±0.3A) (100 mA to 40 A) ±(8% ±0.3A) (40 A to 80 A) |
| AC 20 A range | ±(3% ±5 mA) (10 mA to 10 A, 40 Hz to 2 kHz) ±(4% ±30 mA) (10 mA to 10 A, 2 kHz to 10 kHz) ±(6% ±30 mA) (10 mA to 10 A, 10 kHz to 20 kHz) ±(8% ±30 mA) (10 A to 20 A, 40 Hz to 20 kHz) |
| AC 80 A range | ±(2% ±30 mA) (100 mA to 40 A, 40 Hz to 1 kHz) ±(4% ±30 mA) (100 mA to 40 A, 1 kHz to 3 kHz) ±(6% ±30 mA) (100 mA to 40 A, 3 kHz to 20 kHz) ±(8% ±0.3 A) (40 A to 80 A, 40 Hz to 20 kHz) |
| Output connection | cable with 2 shrouded 4 mm female banana sockets |
Dimensions | |
| Captured conductor size | 12.5 mm maximum |
| Weight | 210 g |
| Height | 38 mm (1.5 inch) |
| Length | 190 mm (7.5 inch) |
| Width | 70 mm (2.8 inch) |
| Length of cable | 30 cm (11.8 inch) |
Power Requirements | |
| Power indicator | Green LED |
| Auto power off | Yes |
| Battery type | Standard 9 V IEC 6F22 cell |
| Battery life | 80 hours typical with alkaline |
| Low battery indication | Red LED |
Ambient | |
| Operating Temperature | 0 to 50 °C |
| Relative Humidity | 25 to 70% |
| Storage Temperature | -20 to 70 °C |
| Relative Humidity | 25 to 80% |
Certifications and Compliances | |
| CE mark compliance | Yes |
| RoHS | Yes |
The Current clamp TP-CC80 is delivered with:
| Amount | Item |
|---|---|
| 1 | Carrying case |
| 1 | Current clamp TP-CC80 |
| Description | Version | Remarks | Size | |
|---|---|---|---|---|
| Current clamp TP-CC80 user manual | 1.3 | English | 305.46 kB | download |